How to Perform a Backflow Prevention Device Test
Learn how to test backflow prevention devices to AS/NZS 2845.3 and AS/NZS 3500.1 standards. Step-by-step compliance testing for Australian licensed plumbers.
Quick answer
Testing a backflow prevention device requires isolating water flow and using a calibrated differential pressure test kit to measure valve thresholds to AS/NZS 2845.3. Technicians verify relief valve opening pressures and check valve seals against backpressure. Results must be lodged annually with the local water authority by an accredited plumber.
- Skill level
- Intermediate
- Time
- 1-2 hours per device (depending on access and device type)
- Trade
- Plumbing
- Updated
- 28 November 2026
Tools you will need
- Watts TK-9A - Digital Differential Pressure Gauge Backflow Test Kit
- Mid-West Model 830 - 5-Valve Backflow Test Kit
- Bahco 8072 - 250mm Adjustable Wrench
- Knipex 87 01 250 Cobra - Water Pump Pliers
- Fluke 62 MAX - Non-Contact Infrared Thermometer
- Pro-Grit Brass Wire Brush - Test Cock Cleaning Brush
- Bolle Safety Rush+ - Clear Safety Glasses
Why is annual backflow prevention device testing mandatory in Australia?
This guide outlines the procedure for performing a backflow prevention device test on an installed backflow prevention assembly in Australia. This is a critical annual compliance task to ensure the device is functioning correctly to protect the potable water supply from contamination.
What skill level is required to perform a backflow prevention device test?
Intermediate — Estimated time: 1-2 hours per device (depending on access and device type)
What essential tools are needed for backflow prevention device testing?
Backflow Test Kit: Calibrated differential pressure gauge with hoses and adaptors (e.g., Watts, Apollo, Conbraco). Must be current with calibration certificate. Wrenches/Spanners: Adjustable spanner or specific spanners for test cocks. Screwdriver Set: For accessing test cock caps if present. Bucket/Container: For collecting discharge water during testing. Cleaning Rags: For wiping down the device and test kit. Clipboard and Pen/Tablet: For recording test results. Backflow Test Report Form: Approved form for recording results (e.g., local council, water authority, or state-specific form). Torch/Headlamp: For inspecting devices in dimly lit areas. Wire Brush: For cleaning test cocks if corroded. Safety Glasses: Eye protection. Gloves: For hygiene and protection.What materials are necessary for a backflow prevention device test?
Backflow Test Report Form: As specified by the relevant water authority (e.g., Sydney Water, Yarra Valley Water, Queensland Urban Utilities). Replacement Test Cock Caps/Seals (Optional): If found to be damaged during inspection. Thread Seal Tape (PTFE): For ensuring watertight connections on test cocks if removed.What safety precautions must be observed when testing backflow prevention devices?
⚠️ Personal Protective Equipment (PPE): Always wear safety glasses and gloves. ⚠️ Pressurised Water: Be aware that the device is under mains pressure. Open test cocks slowly and carefully. ⚠️ Hot Water: If testing a device on a hot water line, be aware of scalding risks. ⚠️ Confined Spaces: If the device is in a confined space, follow all confined space entry procedures. ⚠️ Electrical Hazards: Be aware of any electrical equipment near the device. ⚠️ Slippery Surfaces: Water discharge can create slippery surfaces. ⚠️ Licensing: Plumbing work in Australia must be performed by a licensed plumber. This guide explains the process and helps you select the right tools and materials. Backflow prevention device testing must be performed by a licensed plumber with the appropriate backflow endorsement (e.g., NSW Fair Trading, VIC VBA, QLD QBCC, WA Building Commission).Step-by-Step Guide
Step 1: 1️⃣ Pre-Test Inspection and Site Assessment
Before connecting the test kit, conduct a thorough visual inspection of the backflow prevention device and its surrounding area.
Verify Device Type: Confirm the device type (e.g., RPZD - Reduced Pressure Zone Device, DCV - Double Check Valve, SV - Single Check Valve) matches the site records. Check Installation: Ensure the device is installed correctly according to AS/NZS 3500.1 and manufacturer's instructions (e.g., correct orientation, adequate clearances, air gap for RPZD relief valve). Inspect Condition: Look for any signs of damage, leaks, corrosion, or tampering. Check that all isolation valves are fully open. Identify Test Cocks: Locate and identify all test cocks (typically four for RPZD/DCV). Ensure they are accessible and not seized. Assess Water Supply: Note the water pressure if a gauge is present. Identify the direction of flow. Prepare for Discharge: Position a bucket or container under the relief valve (for RPZD) and test cocks to collect discharged water.Step 2: 2️⃣ Connect the Test Kit
Carefully connect your calibrated backflow test kit to the device's test cocks.
Purge Hoses: Before connecting, briefly open the test kit's hoses to purge any air or debris. Connect Hoses: RPZD/DCV: High-pressure hose (red) to test cock #1 (upstream of the first check valve). Low-pressure hose (blue) to test cock #2 (between the first check valve and the relief valve/second check valve). Differential hose (yellow/black) to test cock #3 (downstream of the relief valve/second check valve). Test cock #4 (downstream of the second check valve) is typically used for the downstream isolation valve test. Ensure all connections are hand-tight and leak-free. Do not overtighten. Open Test Cocks: Slowly open the device's test cocks to allow water into the test kit hoses. Purge any air from the test kit manifold by briefly opening the vent valves on the test kit.Step 3: 3️⃣ Perform the RPZD Test Procedure (Example)
This is a common test procedure for a Reduced Pressure Zone Device (RPZD). Procedures vary slightly for DCV and SV.
Test 1: Relief Valve Opening Point: Close the downstream isolation valve. Slowly open test cock #3 to relieve pressure downstream of the second check valve. Observe the gauge. The relief valve should open and discharge water when the pressure differential between the inlet and the zone (test cock #2) drops to at least 14 kPa (2 PSI) below the inlet pressure. Record the reading. Test 2: First Check Valve Tightness: Close test cock #3. Slowly open test cock #2 to relieve pressure from the zone. The first check valve should hold tight, preventing water from flowing back from the inlet. The gauge reading on test cock #1 and #2 should stabilise, with test cock #2 showing a lower pressure. Record the differential pressure. It should be greater than the relief valve opening point. Test 3: Second Check Valve Tightness: Close test cock #2. Open test cock #3 to relieve pressure downstream. The second check valve should hold tight, preventing water from flowing back from the zone. Record the differential pressure between test cock #2 and test cock #3. It should be positive. Test 4: Downstream Isolation Valve Tightness: With the device under pressure and the downstream isolation valve closed, open test cock #4. There should be no flow from test cock #4, indicating the downstream isolation valve is holding tight.Step 4: 4️⃣ Record Results and Complete Documentation
Accurately record all readings and observations on the approved backflow test report form.
Fill in Details: Complete all sections of the form, including site address, device type, serial number, location, date, and your licence details. Record Readings: Document the pressure readings for each test step. Note Observations: Record any issues found during the pre-test inspection or during the test (e.g., leaks, relief valve weeping, seized test cocks). Pass/Fail: Clearly indicate whether the device passed or failed the test. Sign Off: Sign and date the report. Provide a copy to the client and submit to the relevant water authority as required.Step 5: 5️⃣ Restore System and Disconnect Test Kit
Once testing is complete, carefully restore the system to normal operation.
Close Test Cocks: Slowly close all test cocks on the backflow prevention device. Close Test Kit Valves: Close all valves on your backflow test kit manifold. Disconnect Hoses: Carefully disconnect the test kit hoses from the device's test cocks. Replace Caps: Replace any test cock caps that were removed. Open Isolation Valves: Ensure both upstream and downstream isolation valves are fully open. Check for Leaks: Visually inspect the device and connections for any leaks. Clean Up: Clean the device and surrounding area. Pack away your tools.Common Mistakes to Avoid
Pro Tips
💡 Pre-Calibrate: Always check your test kit's calibration certificate before heading to a job. Keep a copy with your kit. 💡 Lubricate Test Cocks: If test cocks are stiff, a small amount of food-grade silicone grease can help, but avoid over-lubricating which can attract dirt. 💡 Carry Spares: Keep a small stock of common test cock caps and seals. 💡 Digital vs. Analogue: Digital test kits offer greater precision and often have data logging capabilities, but require battery management. Analogue gauges are robust and don't require power. 💡 Customer Communication: Clearly explain the test process and any findings to the client, especially if a device fails and requires repair or replacement. 💡 Water Efficiency: While testing, minimise water wastage. Collect discharge water in a bucket for reuse if possible, especially for multiple tests.Recommended Tools
Watts Series 900 Backflow Test Kit: A widely recognised and reliable differential pressure gauge for accurate testing. Ridgid 31090 Model 818 Aluminum Straight Pipe Wrench: Essential for securely opening and closing isolation valves if they are stiff. Milwaukee M12™ Compact Digital Inspection Camera: Useful for inspecting hard-to-reach areas or internal components if a device is disassembled for repair.Frequently asked questions
- What is the Australian standard for testing backflow prevention devices?
- Backflow prevention devices in Australia must be field tested in accordance with AS/NZS 2845.3:2020. General installation, maintenance, and hazard ratings are governed by AS/NZS 3500.1:2021 and the Plumbing Code of Australia (PCA). These standards mandate strict testing sequences and minimum pressure differentials to verify check valves and relief ports.
- How often does a backflow prevention device need testing in Australia?
- Testable backflow prevention devices must be tested annually across all Australian states and territories. Testing is also legally required immediately after initial installation, relocation, or any mechanical repair. Results must be submitted directly to the relevant local water authority, such as Sydney Water, Urban Utilities, or Yarra Valley Water.
- Who is legally allowed to test backflow devices in Australia?
- Only a licensed plumber who holds an accredited Backflow Prevention endorsement can test or certify backflow containment devices in Australia. Testers must complete the nationally recognised unit CPCPWT4022 and register annually with their state licensing regulator, such as the Victorian Building Authority (VBA) or Queensland Building and Construction Commission (QBCC).
- How do you test a Reduced Pressure Zone Device (RPZD)?
- Testing an RPZD involves verifying the differential pressure across the first check valve, checking the relief valve opening point, and confirming the second check valve holds against backpressure. A calibrated differential pressure gauge connects via test cocks to measure that the relief valve opens at a minimum of 14 kPa.
- What are the most common reasons backflow devices fail testing?
- Backflow devices most commonly fail due to line debris lodging under check valve elastomers, preventing a tight seal. Scale build-up on seats, perished rubber discs, and worn internal springs also cause pressure drops below statutory thresholds. Annual line flushing prior to testing helps prevent false failures caused by loose sediment.
- What happens if a property owner fails to complete annual backflow testing?
- Failure to complete annual backflow testing leads to non-compliance notices, substantial fines, and potential disconnection of the property water service by the water authority. In the event of a cross-contamination incident, uncertified properties face severe civil liabilities and breaches of state public health legislation.
Written by Pipey, the Plumbing specialist at VIC.Tools.