How to replace a burst flexi hose

Burst flexi hoses are a common emergency failure point under basins, sinks, toilets and mixers, and can cause major internal water damage within minutes. Plumbing work in Australia must be performed by a licensed plumber. This guide explains the process and helps you select the right tools and mater

Skill level
Intermediate
Time
0.5 to 2 hours for a standard replacement, plus additional time for access, drying, documentation and any valve rectification
Trade
Plumbing
Updated
28 November 2026

Tools you will need

  • Adjustable spanners
  • Water pump pliers
  • Basin spanner
  • Inspection torch / headlamp
  • Inspection mirror
  • Bucket
  • Wet vacuum
  • Absorbent towels / spill mats
  • Water pressure gauge
  • PTFE tape and/or approved thread sealant

πŸ”§ Trade guide for replacing a burst flexi hose on Australian fixtures and taps

What is involved in replacing a burst flexi hose?

Burst flexi hoses are a common emergency failure point under basins, sinks, toilets and mixers, and can cause major internal water damage within minutes. Plumbing work in Australia must be performed by a licensed plumber. This guide explains the process and helps you select the right tools and materials.

This guide is written for Australian trade professionals and references the PCA, AS/NZS 3500.1, AS/NZS 3500.4 and AS/NZS 3499 for compliant water supply repair, product selection and recommissioning.

What skill level is required to replace a burst flexi hose?

Intermediate β€” Estimated time: 0.5 to 2 hours for a standard replacement, plus additional time for access, drying, documentation and any valve rectification

What tools are essential for replacing a burst flexi hose?

Adjustable spanners β€” 150 mm and 250 mm, smooth-jaw preferred for chrome protection
Water pump pliers β€” 250 mm capacity for valve restraint and locknut control
Basin spanner β€” essential for tight vanity and sink cabinet access
Inspection torch / headlamp β€” high-output LED for underside and rear cabinet inspection
Inspection mirror β€” for checking mixer tails, stop taps and concealed thread alignment
Bucket β€” minimum 10 L
Wet vacuum β€” for immediate flood extraction and cabinet clean-up
Absorbent towels / spill mats β€” to protect cabinetry and flooring
Water pressure gauge β€” suitable for domestic testing up to at least 1,600 kPa
PTFE tape and/or approved thread sealant β€” only where threaded joint design requires it
Camera or mobile device β€” for insurance documentation and condition photos
Tagging pen / label β€” to record replacement date if required by maintenance program

What materials are needed for a compliant flexi hose replacement?

1 x replacement flexi hose / braided tap connector, WaterMark certified, compliant with AS/NZS 3499
Match existing end connections exactly, commonly:
DN15 (1/2 in BSP) female x DN15 (1/2 in BSP) female
DN15 (1/2 in BSP) female x M10 or M12 mixer tail
20 mm (3/4 in BSP) where applicable on some appliance or cistern connections
Replacement captive cone washers / fibre washers / flat washers as required by hose type
1 x mini stop / isolation valve if the existing valve is seized, leaking, unserviceable or non-compliant
Olive and compression nut if replacing a compression stop valve on 15 mm copper
Approved thread sealant for tapered threads only
Chrome cover plate / dressing flange if disturbed during valve replacement
Moisture-control consumables β€” disinfectant wipe, cabinet liner, drying cloths
Optional pressure limiting valve if static pressure exceeds compliant limits under AS/NZS 3500.1
Optional hammer arrestor / valve upgrade components where repeated hose failure is linked to surge or valve slam

Safety Requirements

Isolate the water supply immediately and confirm pressure is relieved before disconnecting any hose.
Treat burst-hose callouts as both a plumbing emergency and a property-damage event. Protect flooring, cabinetry, power points and adjacent joinery.
If flooding is near electrical outlets, appliances, dishwashers, insinkerators or GPOs, isolate the affected electrical circuit before commencing work.
Hot water flexi failures can discharge at scalding temperature. Use gloves and relieve pressure carefully.
Confirm the replacement hose is WaterMark certified and compliant with AS/NZS 3499.
Installation and testing of water services must align with the PCA and AS/NZS 3500 series.
Do not use a flexi hose where rigid connection, support, temperature rating or exposure conditions make it unsuitable.
Flexi hoses must not be installed under torsion, sharp bend, abrasion, UV exposure or contact with hot surfaces.
πŸ”’ Licensing: Plumbing work in Australia must be carried out by a licensed plumber in accordance with state and territory requirements, including NSW Fair Trading, VIC VBA, QLD QBCC and WA Building Commission.
Gas work requires a separate gas fitter licence and is outside the scope of this water supply repair guide.

Step-by-Step Guide

Step 1: 1️⃣ Make the Site Safe and Isolate the Water

Attend the failure as an emergency response. Shut the nearest fixture isolation valve first if it is operational. If the mini stop has failed, is seized, or will not fully close, isolate the branch line or the main water supply to the premises.

Open the affected tap or fixture outlet to relieve residual pressure. If the burst hose is on a hot service, allow temperature to stabilise before handling. Use a 10 L bucket, wet vacuum and absorbent towels to control ongoing discharge and prevent secondary damage.

Photograph the failed hose in situ before removal. Record the location, extent of visible water damage, and whether the hose failed at the crimp, braid, inner tube, swivel or mixer tail. This is valuable for client records, warranty review and insurance reporting.

Step 2: 2️⃣ Confirm the Cause of Failure and Replacement Specification

Do not assume the hose alone is the only issue. Inspect the full connection assembly, including the stop valve, mixer tail, cistern cock, tap body, bracket support and cabinet penetrations.

Identify:

Hose length and routing
End connection types
Thread form and sealing method
Pressure and temperature exposure
Evidence of twisting, kinking, over-tightening, corrosion or abrasion
Static pressure concerns, hammer or valve slam
Whether the failed hose is part of a matched hot/cold pair

Check the product marking on the failed connector. Replacement must be the correct length and connection type, and must be WaterMark certified to AS/NZS 3499. If the hose is integral to the mixer and not designed for separate replacement, replace the mixer or fixture assembly instead of attempting an improvised repair.

πŸ’‘ If one hose on a mixer has burst, the matching hose is often of the same age and service history. For trade risk management, recommend replacing both at the same visit where practical.

Step 3: 3️⃣ Remove the Failed Flexi Hose

Place a bucket under the work area and back up the isolation valve or tap body with a second spanner to avoid transmitting torque into the pipework or fixture.

Disconnect the hose from the outlet side first where access allows, then from the valve side. In vanity and sink cabinets, a basin spanner may be required to access the mixer tail or retaining area without damaging the tap body.

Inspect the joint faces after removal:

Swivel nuts for thread damage
Captive cone or flat washers for extrusion or hardening
Valve outlet seating face for burrs or corrosion
Mixer tail threads for stripping or cross-threading
Signs of dezincification or cracking on brass components

Do not reuse damaged washers. If the stop valve spindle leaks, outlet thread is pitted, or the body is unstable, replace the valve rather than fitting a new hose to a defective termination point.

Step 4: 4️⃣ Rectify Any Contributing Defects Before Reinstallation

A burst flexi hose is often a symptom rather than the sole defect. Before fitting the new connector, rectify any of the following:

Seized or leaking mini stop
Unsupported or loose tap body
Excessive static pressure
Poor routing causing constant torsion
Contact with cabinet edges or cleaning chemicals
Heat exposure near boiling water units or hot pipework

Test or record the static pressure if not already known. Under AS/NZS 3500.1, excessive pressure may require a pressure limiting solution. If the service pressure is above compliant fixture limits, replacing the hose without addressing pressure is poor trade practice and increases repeat-failure risk.

Where a compression mini stop is replaced on 15 mm copper, cut back to clean tube if required, fit a new olive, and ensure the outlet orientation allows a natural hose path with no side load.

Step 5: 5️⃣ Install the New Flexi Hose Correctly

Fit the new hose with the correct sealing method for the connection type.

For swivel-nut connections with captive washer or cone seal:

Do not apply PTFE tape to the thread
Ensure the sealing face is clean
Hand-start the thread to avoid cross-threading
Tighten to firm manufacturer-recommended tension without over-compressing the seal

For tapered threaded connections:

Apply approved thread sealant or PTFE tape as appropriate
Engage threads cleanly and avoid forcing misaligned fittings

Route the hose in a smooth natural curve. Do not install under twist. A common trade method is to align the hose first, then tighten while holding the braid so the connector does not wind up.

Maintain adequate bend radius per manufacturer instructions. The hose must not:

kink
rub on sharp cabinet penetrations
bear the weight of the tap body
touch heated surfaces
be stretched to reach the connection

If replacing paired hot and cold connectors on a mixer, keep hose routing symmetrical and ensure neither hose crosses in a way that creates abrasion or future service issues.

Step 6: 6️⃣ Recommission, Pressure Test and Check for Leaks

With all joints tightened and the fixture outlet open, slowly restore water supply to minimise shock loading. Crack the isolation valve gradually rather than opening it suddenly.

Bleed air through the fixture and inspect all joints under static and flowing conditions. Wipe each connection dry, then recheck for weeping with a torch and tissue. Pay particular attention to:

valve outlet connection
mixer tail connection
stop valve spindle
adjacent fittings disturbed during the repair

If servicing a hot connection, run hot water long enough to confirm the hose remains stable under temperature. Where a tempering or thermostatic mixing arrangement is part of the system, confirm downstream delivery remains consistent with the existing installation under AS/NZS 3500.4.

Step 7: 7️⃣ Document the Repair and Manage Post-Flood Requirements

Complete the callout professionally by documenting:

failed hose type and location
product markings
cause of failure if identifiable
pressure readings if taken
associated rectification completed
photos before and after repair

Advise the client on drying, cabinet inspection and any need for insurer notification where water damage is evident. If joinery, skirting, plasterboard or flooring has been affected, note that plumbing repair does not remove the need for moisture remediation.

Where relevant, label or record the installation date of the replacement hose for maintenance tracking. In commercial settings or high-risk properties, recommend scheduled inspection of other braided connectors of similar age.

What are common mistakes to avoid when replacing a flexi hose? to Avoid

1.Replacing the hose without checking the stop valve, mixer tail or seating surface that caused the failure or leak path.
2.Using PTFE tape on washered swivel-nut connections that are designed to seal on the washer, not the thread.
3.Installing the new hose under twist, sharp bend or tension, which significantly shortens service life.
4.Matching only the hose length and ignoring end connection type, pressure rating, temperature rating or WaterMark compliance.
5.Failing to check supply pressure and water hammer where repeated flexi hose failures have occurred.
6.Leaving the matching hose in service when it is the same age, brand and duty as the burst hose.
7.Not documenting water damage and failed component condition for insurance, warranty or client records.

Pro Tips

πŸ’‘ Carry a stock range of DN15 (1/2 in BSP) flexi connectors in multiple lengths, plus M10 and M12 mixer-tail variants, to reduce second-visit delays on emergency callouts.
πŸ’‘ On insurance-sensitive jobs, photograph the failed crimp, braid and connection faces before disposal. Product failure patterns matter.
πŸ’‘ If a mini stop is old or partly seized, replace it during the same visit. A new hose connected to a marginal valve often leads to a return call.
πŸ’‘ Measure and record static pressure on repeat burst-hose sites. Chronic high pressure is a common root cause and should be rectified, not ignored.
πŸ’‘ Where associated tapware is being replaced, specify equal or better WELS performance than existing fixtures. For many basins, 5 Star or 6 Star WELS mixers are a strong water-efficiency upgrade.
πŸ’‘ In commercial or strata environments, recommend periodic audit and planned replacement of aged braided connectors rather than waiting for failure.

Recommended Tools

Knipex Cobra 250 mm water pump pliers β€” excellent grip for restraining valves without excessive slip
Bahco 6 in and 10 in adjustable spanners β€” reliable for tap connectors and mini stops in confined spaces
RIDGID basin wrench / basin spanner β€” ideal for mixer tail access in tight vanity cabinets
Test gauge with hose bibb adaptor, 0–1600 kPa β€” essential for diagnosing overpressure-related hose failures
Compact wet vacuum β€” fast water extraction to reduce secondary damage during emergency callouts

Frequently asked questions

What is involved in replace a burst flexi hose?
Burst flexi hoses are a common emergency failure point under basins, sinks, toilets and mixers, and can cause major internal water damage within minutes. Plumbing work in Australia must be performed by a licensed plumber. This guide explains the process and helps you select the right tools and mater
What skill level do I need for replace a burst flexi hose?
Intermediate β€” Estimated time: 0.5 to 2 hours for a standard replacement, plus additional time for access, drying, documentation and any valve rectification
What are common mistakes when replace a burst flexi hose?
1. Replacing the hose without checking the stop valve, mixer tail or seating surface that caused the failure or leak path. 2. Using PTFE tape on washered swivel-nut connections that are designed to seal on the washer, not the thread. 3. Installing the new hose under twist, sharp bend or tension, which significantly shortens service life. 4. Matching only the hose length and ignoring end
What tools do I need for replace a burst flexi hose?
This guide includes a comprehensive tools list. Key plumbing tools are detailed in the Tools Required section.
What is the Australian standard for flexible hose assemblies?
The Australian standard for flexible hose assemblies used in water installations is AS/NZS 3499:2006. This standard specifies requirements for materials, construction, and performance, ensuring products are fit for purpose and comply with the WaterMark Certification Scheme. Always verify that replacement hoses carry the WaterMark logo for compliance.
Why is WaterMark certification important for flexi hoses?
WaterMark certification is crucial for flexi hoses as it confirms the product complies with Australian plumbing standards, including AS/NZS 3499. According to the Plumbing Code of Australia (PCA), only WaterMark certified products can be installed in plumbing and drainage systems, guaranteeing safety, quality, and fitness for purpose.
How often should flexi hoses be inspected or replaced?
While there's no mandatory replacement schedule, the Plumbing Code of Australia (PCA) recommends regular inspection of flexible hoses, especially after 5-10 years of service. Factors like water pressure, installation quality, and environmental conditions can influence lifespan. Proactive replacement of older hoses can prevent catastrophic failures and water damage.
Can I replace a burst flexi hose myself in Australia?
No, in Australia, plumbing work, including the replacement of a burst flexi hose, must be carried out by a licensed plumber. This is a legal requirement under state and territory plumbing regulations to ensure safety, compliance with AS/NZS 3500, and to prevent potential health hazards or property damage from incorrect installation.

Written by Pipey, the Plumbing specialist at VIC.Tools.